Model 419 | Smart A/D

Model 419 |  Smart A/D Features
  • Supports thermocouples, RTD’s, strain gauges, voltage in, 4-20 mA, thermistors, and resistors
  • 16 differential input channels plus sensor excitation
  • Each channel is software programmable for sensor type, gain, low-pass filtering, scan rate
  • Auto-calibration eliminates trimpots
  • Low power consumption

Description

The Sensoray Models 419 offer a cost-effective way to acquire sensor data for any ISA bus system. They features 16-bit resolution from 16 channels, each individually programmable for a different sensor type. Analog-to-digital conversion is performed in under 22 milliseconds, providing 45 channels per second scan rate.

The 419 adapters plug directly into any half slot ISA computer. Linearization, calibration, and sensitivity are software program- mable, eliminating trim potentiometers and the need for board access. Sensor field wiring is accomplished with a 40-conductor flat cable and remotely mountable screw- termination board, either model 7409TB or model 7409TDIN with DIN rail mounting hardware.

Calibration
Models 419 automatically self- calibrate by measuring internal precision references. Reference data is stored in EEPROM so the adapter boards may be easily interchanged. Signal conditioning is provided for thermistors, RTD’s, thermocouples, strain and pressure, resistance and voltage inputs. Standard correction for nonlinear sensors is built in. Custom compensation can be down loaded.

Excitation
A pulsed constant-voltage source is provided for strain and pressure sensors. A pulsed constant-current source is provided for resistive sensors. Lead loss errors from RTD’s, thermistors, and resistors are eliminated with the use of a four-wire circuit.

An on-board microprocessor continually scans the active sensor channels. Each channel is amplified, digitized, filtered, converted to engineering units, and stored in on-board memory. This process is independent of host CPU activity.

Application Notes
Thermocouples >> Lead loss errors >> Typical sensor connections

Software & Manuals
 An optional data logging program, QuickSense, allows easy channel definition and data readback.

418/419 Instruction Manual >> Released 3/11/04
SDK18 (32-bit DLLfor Windows 95/98/NT) >> Released 5/1/03
Quicksense Software >> Released 12/15/99

 

Mechanical Drawings and Images
Typical Application
Sensor Connector Pinout

 

General Specifications

 

 

 

Input resistance

1000 Megohms

 

 

Max. input voltage

63 VAC rms

 

 

CMMR

95 db min

 

 

Max. command mode

+/- 5 volts

 

 

A/D converter

16-bit integrating

 

 

Conversion time

22 mS per channel

 

 

A/D scan rate

45 samples/sec

 

 

Operating temperature

-25°C to 85°C

 

 

PC/104 interface

2 I/O ports

 

 

Input power

5 volts at 100 mA  | 12 volts at 45 mA

 

 

For Sensor Types, Resolution, Range and Codes click here

Details

SKU SKU16959
Weight 300.00 g
Single item price(ex. VAT): €456.00


Contact us for availability


 

Send to colleague
Your name: *
Your e-mail: *
Recipient's email: *

Send to colleague
 

 


Copyright © 2006-2012 Enciris Technologies, SAS
 
|    Enciris Home  |    Sensoray Video  |    Sensoray Industrial I/O  |    All Sensoray  |    Shopping Cart  |    Contact Us  |    About us  |